PS 200 Configuration
The PS 200 must have a RMBA-01 Modbus adapter module installed in slot 1 for Modbus communication over RS-485.
Set the following parameters in the PS 200 device:
Parameter | Parameter name | Setting |
30.01 | FIELBUS | STD MODBUS |
30.03 | COMM PROFILE | CSA2.8/3.0 |
52.01 | STATION NUMBER | User defined |
52.02 | BAUD RATE | 9600 |
52.03 | PARITY | NONE1STOPBIT |