EcoTouch Configuration
The unit is connected to this device with RS-485 through the following terminals.
| Terminal | Description | 
| ST5 pin 5/6 | RS-485(A) | 
| ST5 pin 7/8 | RS–485(B) | 
| ST5 pin 3/4 | GND | 
| ST5 pin 9/10 | Termination (120R) | 
Termination must be activated by a wire jumper between ST5 pin 9/10 and ST5 pin 7/8.
- On the EcoTouch screen, go to Menu > I/O Setting, page 3.
- Click Avensor Mode.
- Select OFF or Monitor only or Monitor & Control
- Press Enter.
- Set the communication parameters.
| Parameter | Setting | 
| Modbus Device Address | 1 | 
| Baud rate | 9600 | 
| Parity | None | 
| Stop bits | 1 |