MAS 711 Configuration
The unit is connected to this device through the following terminals:
| Terminal | Description | 
| 41 | Ext. 1, RS-584 (A) | 
| 42 | Ext. 1, RS-485 (B) | 
- Click Settings > General configuration > RS485/ Modbus.
- In Higher level controller (External 1) group, set the following parameters:
| Parameter | Setting | 
| Activate | Active | 
| Baudrate | 9600 or 19200 | 
| Modbus protocol | MAS Modbus revision 3 | 
| Address (MAS Modbus ID) | 1 to 247 | 
- Click Update.
- Click Restart to execute the settings.