XCU 411 Configuration
- Prepare a configuration file.
 Configuration Instructions Standard configuration Download the configuration file from TPI. Custom configuration - Insert a USB drive into the XCU 411. When the LED on the USB icon goes from flashing green to steady green, the file is exported to the USB drive.
- Use a text editor to edit the settings in this section of the configuration file:
 
 "IP Address": "10.10.10.10",
 "IP Subnet Mask": "255.255.255.0"},
 "Modbus": { "RTU": {
 "Parity": "NONE",
 "Unit ID": 1,
 "Baudrate": 9600,
 "RS485 Port Termination": false},
 "TCP Port": 502
- Put the configuration file in the root directory of a USB drive.
- Turn off the power to the XCU 411.
- Insert the USB drive into the XCU 411.
- Turn on the XCU 411.
 When the LED on the USB icon goes from flashing green to steady green, the update is completed.