Hydrovar HVL Configuration

On the Hydrovar HVL device, the up and down key must be pressed to change the submenus.

  1. Go to M1200 RS-485 INTERFACE.
  2. Set the following parameters.
ID Parameter Setting
P24 Enable Device Enabled
P105 Mode Controller or Cascade
P202 Software V2.0 or higher
P210 Inverter All
P1203 Protocol Modbus RTU
P1205 Address 1
P1210 Baud rate 9600
P1215 Format 8,N.1
P1310 Pump Address 1
P1321 Auto-start ON
P1323 Address 1