PS 220 Configuration
The user can choose between TCP or RTU Modbus communication
Modbus TCP
The FMBT-21 device must be installed in slot 2.
Set the following parameters.
| Parameter | Parameter name | Setting |
| 50.1 | FBA A ENABLE | [2] Option slot 2 |
| 74.01 | START/STOP | [6] Fieldbus |
| 74.05 | SPEED OVERRIDE | [6] Fieldbus |
| 74.06 | SPD OVERRIDE | [3] Fieldbus |
| 51.01 | FBA A type | [128] Ethernet |
| 51.02 | Protocol/Profile | [1] MB/TCP ABB E |
| 51.03 | Commrate | [0] Auto |
| 51.04 | IP configuration | [0] Static IP |
| 51.05 | IP address 1 | 10 |
| 51.06 | IP address 2 | 10 |
| 51.07 | IP address 3 | 10 |
| 51.08 | IP address 4 | 20 |
| 51.09 | Subnet CIDR | 24 |
| 51.22 | Word order | 1 = HILO |
| 51.23 | Address mode | [1] Mode 1 |
| 51.27 | FBA A par refresh | [1] Refresh |
Modbus RTU
The FSCA-module must be installed in slot 2.
Set the following parameters.
| 50.1 | FBA A ENABLE | [2] Option slot 2 |
| 74.01 | START/STOP | [6] Fieldbus |
| 74.05 | SPEED OVERRIDE | [6] Fieldbus |
| 74.06 | SPD OVERRIDE REF | [3] Fieldbus |
| 51.01 | FBA A type | [485] FSCA |
| 51.02 | Protocol/Profile | [1] MB/TCP ABB E |
| 51.03 | Station ID | 1 |
| 51.04 | Baud | 9600 |
| 51.05 | Parity | None |
| 51.25 | Protocol | [1] Modbus |
| 51.27 | FBA A par refresh | [1] Refresh |