Hydrovar HVL Configuration
On the Hydrovar HVL device, the up and down key must be pressed to change the submenus.
- Go to M1200 RS-485 INTERFACE.
- Set the following parameters.
ID | Parameter | Setting |
P24 | Enable Device | Enabled |
P105 | Mode | Controller or Cascade |
P202 | Software | V2.0 or higher |
P210 | Inverter | All |
P1203 | Protocol | Modbus RTU |
P1205 | Address | 1 |
P1210 | Baud rate | 9600 |
P1215 | Format | 8,N.1 |
P1310 | Pump Address | 1 |
P1321 | Auto-start | ON |
P1323 | Address | 1 |