MAS 711 Configuration
The unit is connected to this device through the following terminals:
Terminal | Description |
41 | Ext. 1, RS-584 (A) |
42 | Ext. 1, RS-485 (B) |
- Click Settings > General configuration > RS485/ Modbus.
- In Higher level controller (External 1) group, set the following parameters:
Parameter | Setting |
Activate | Active |
Baudrate | 9600 or 19200 |
Modbus protocol | MAS Modbus revision 3 |
Address (MAS Modbus ID) | 1 to 247 |
- Click Update.
- Click Restart to execute the settings.